__NOTOC__ The mean radiant temperature (MRT) is defined as the uniform temperature of an imaginary enclosure in which the radiant heat transfer from the human body is equal to the radiant heat transfer in the actual non-uniform enclosure.〔 MRT is a concept arising from the fact that the net exchange of radiant energy between two objects is approximately proportional to their temperature difference multiplied by their ability to emit and absorb heat (emissivity). It is simply the area weighted mean temperature of all the objects surrounding the body. This is valid as long as the absolute temperatures of objects in question are large compared to the temperature differences, allowing linearization of the Stefan-Boltzmann Law in the relevant temperature range. MRT also has a strong influence on thermophysiological comfort indexes such as physiological equivalent temperature (PET) or predicted mean vote (PMV). What we experience and feel relating to thermal comfort in a building is related to the influence of both the air temperature and the temperature of surfaces in that space. The mean radiant temperature is expressed as this surface temperature and is controlled by enclosure performances. Maintaining a balance between the operative temperature and the mean radiant temperature can create a more comfortable space. This is done with effective design of the building, interior and with the use of high temperature radiant cooling and low temperature radiant heating. == Calculation == There are different ways to estimate the mean radiant temperature, either applying its definition and using equations to calculate it, or measuring it with particular thermometers or sensors. Since the amount of radiant heat lost or received by human body is the algebraic sum of all radiant fluxes exchanged by its exposed parts with the surrounding sources, MRT can be calculated from the measured temperature of surrounding walls and surfaces and their positions with respect to the person. Therefore, it is necessary to measure those temperatures and the angle factors between the person and the surrounding surfaces.〔 Most building materials have a high emittance ε, so all surfaces in the room can be assumed to be black. Because the sum of the angle factors is unity, the fourth power of MRT equals the mean value of the surrounding surface temperatures to the fourth power, weighted by the respective angle factors. The following equation is used:〔〔2009 ASHRAE Handbook Fundamentals, ASHRAE, Inc., Atlanta, GA.〕 where: : is Mean Radiant Temperature; : is the temperature of surface "n", in Kelvins; : is the angle factor between a person and surface "n". If relatively small temperature differences exist between the surfaces of the enclosure, the equation can be simplified to the following linear form:〔〔 This linear formula tends to give a lower value of MRT, but in many cases the difference is small.〔 In general, angle factors are difficult to determine, and they normally depend on the position and orientation of the person.Furthermore, this method becomes complex and time consuming as the number of surfaces increases and they have elaborate shapes. For this reason, an easier way to determine the MRT is by measuring it with a particular thermometer. 抄文引用元・出典: フリー百科事典『 ウィキペディア(Wikipedia)』 ■ウィキペディアで「Mean radiant temperature」の詳細全文を読む スポンサード リンク
|